Contact Sales 0800 970 4190
The HRV10.25 Q Plus continuously running whole-house ventilation unit with heat recovery has been specifically designed to give improved performance over older models, in line with new build design requirements.
Combining extremely low power consumption and a highly efficient heat exchanger specifically designed to enhance SAP performance via Appendix Q and can be incorporated into larger apartments or dwellings.
The HRV10.25 Q Plus Range of MVHR unit comes in two different models; the ‘HMB’ & ‘B’ models which are part of our Eco version range. Each set out to accommodate our customers’ needs.
Recognised and listed in the UK Product Characteristics Database and includes intelligent humidity options through controller options.
The HRV10.25 Q Plus is also available with an enthalpy cross flow exchanger, which transfers thermal and latent energy of the extracted air to the incoming air, which is then distributed to the habitable rooms via ducts. Using Microban® technology it protects against mould and bacteria whilst recycling moisture back into a dwelling to allow homes with low humidity to achieve a sufficient comfortable level.
| Product Model | Product Code | Energy Rating |
| HRV10.25 Q Plus HMB Eco auralite® & aura-t™ ready |
TP442HMB | Energy Rating A |
| Product Model | Product Code | Energy Rating |
| HRV10.25 Q Plus B Eco-aura controls ready |
TP482B | Energy Rating A |
| HRV10.25 Q Plus B Eco Enthalpy Eco-aura controls ready |
TP482BE | Energy Rating A |
| HRV10.25 Q Plus B Eco-aura controls Cold Climate ready |
TP482BC | Energy Rating A |
XP44023/099 - ISO Coarse 65% (G4) bypass filter set fitted as standard.
XP46223/099 - ISO Coarse 65% (G4)/ISO ePM1 55% (F7) filters available on request.
Conforms to requirements of UK statutory Building Regulations and Technical Standards for Ventilation and BRE 398.
SAP Appendix Q tested
Exceeds requirements of Building Regulations Approved Document L (England & Wales).
EU RoHS Directive compliant.
Conforms to requirements of EC council directives relating to Electromagnetic Compatibility and Electrical Safety:
2006/95/EC (LVD), 2004/108/EC (EMC), EN 60335-1:2002/A2:2006, EN 60335-2- 80:2003/A1:2004.
CE and UKCA Marked.
Dimensions: 790mm wide x 663mm high (excluding ports) x 484mm deep (495mm with mounting bracket).

Weight: 18kg.
Finish: Black EPP.
Materials:
Housing: Expanded polypropylene (EPP) housing
Heat exchanger: Polystyrene
Internal insulation: Closed cell foamed Nitrile rubber, class ‘O’ fire rating
Standard filters: Grade ISO Coarse 65% (G4) pleated panel filters.
Guarantee period: 3 years (UK only).
Electrical: 230V ~ 50/60Hz, 5A fuse.
Installation: To be installed accordance with the relevant and applicable building regulations.
Maintenance: Service and clean/replacement subject to local environment – see product manual.
Acoustics: Full acoustic data.
|
Exhaust terminal configuration*
|
Fan speed setting
|
Specific fan power (W/l/s)
|
Heat exchange efficiency (%)
|
Specific fan power (W/l/s)
|
Heat exchange efficiency (%)
|
|
2009
|
2012
|
||||
|
Kitchen + 1 additional wet room
|
100% variable
|
0.41
|
90%
|
0.43
|
90%
|
|
Kitchen + 2 additional wet room
|
100% variable
|
0.39
|
90%
|
0.46
|
88%
|
|
Kitchen + 3 additional wet room
|
100% variable
|
0.43
|
88%
|
0.54
|
87%
|
|
Kitchen + 4 additional wet room
|
100% variable
|
0.48
|
87%
|
0.65
|
86%
|
|
Kitchen + 5 additional wet room
|
100% variable
|
0.55
|
87%
|
0.79
|
85%
|
|
Kitchen + 6 additional wet room
|
100% variable
|
0.64
|
86%
|
0.96
|
84%
|
|
Kitchen + 7 additional wet room
|
100% variable
|
0.75
|
85%
|
1.16
|
83%
|
Figures taken from the BRE Test Results.
*Number of wet rooms is based on SAP Q test criteria and does not correlate directly with regulatory performance requirements.


*@FID (0 Pa)
All units offer 100% variable speed control
|
Product
|
% of Max flow
|
Airflow
|
dB(A) @ 3m Hemispherical
|
dB(A) @ 3m Spherical
|
||
|
Induct
Inlet |
Induct
Outlet |
Casing
Breakout |
Casing Breakout
|
|||
|
HRV10.25 Q Plus Eco
|
39%
|
56l/s @ 12Pa
|
32
|
47
|
35
|
32
|
|
66%
|
95l/s @ 44Pa
|
43
|
62
|
45
|
42
|
|
|
100%
|
144l/s @ 100Pa
|
48
|
70
|
54
|
51
|
|
All acoustic data is third party tested at Sound Research Laboratories (SRL) Ltd.