Contact Sales 0800 970 4190
Suitable for larger dwellings, the HRV3 Q Plus continuously running whole-house ventilation unit with heat recovery is independently tested by the BRE. The HRV3 Q Plus gives cutting edge performance usually only associated with much larger and more costly products.
The combination of very low power consumption and a highly efficient heat exchanger is specifically designed to enhance SAP performance via Appendix Q, yet small enough to be easily incorporated into medium to large sized dwellings.
The HRV3 Q Plus Range of MVHR unit comes in three different models; our ‘A’ model which is our basic version and our ‘HMB’ & ‘B’ models which are part of our Eco version range. Each set out to accommodate our customers’ needs.
Recognised and listed in the UK Product Characteristics Database and includes intelligent humidity options through controller options.
The HRV3 Q Plus is also available with an enthalpy cross flow exchanger, which transfers thermal and latent energy of the extracted air to the incoming air, which is then distributed to the habitable rooms via ducts. Using Microban® technology it protects against mould and bacteria whilst recycling moisture back into a dwelling to allow homes with low humidity to achieve a sufficient comfortable level.
| Product Model | Product Code | Energy Rating |
| HRV3 Q Plus | TP402A | Energy Rating B |
| Product Model | Product Code | Energy Rating |
| HRV3 Q Plus HMB Eco auralite® & aura-tTM ready |
TP402HMB/544 (left hand config) |
Energy Rating A |
| TP402HMB/RH (right hand config) |
| Product Model | Product Code | Energy Rating |
| HRV3 Q Plus B Eco-aura controls ready | TP412B/LH (left hand config) |
Energy Rating A |
| TP412B/RH (right hand config) |
||
| HRV3 Q Plus B Eco-aura controls Cold Climate ready | TP412BC | Energy Rating A |
| HRV3 Q Plus B Eco Enthalpy Eco-aura controls ready | TP412BE/LH (left hand config) |
Energy Rating A |
| TP412BE/RH (right hand config) |
||
| HRV3 Q AR Plus Eco | TP412BAR/BEL LH (left hand config) |
Energy Rating A |
| TP412BAR/BEL RH (right hand config) |
XP40132/099 - ISO Coarse 55% (G3) filters fitted as standard (UK only).
XP46122/099 - ISO Coarse 60% (G4) filters fitted on request (Europe fitted as standard).
XP40133/099 - ISO Coarse 55% (G3) filters fitted as standard (UK only).
XP46133/099 - ISO Coarse 60% (G4) filters fitted on request (Europe fitted as standard).
XP46222/099 - ISO Coarse 55% (G3)/ISO ePM1 55% (F7) filters available on request.
XP46232/099 - ISO Coarse 60% (G4) filters/ISO ePM1 55% (F7) filters available on request.
Conforms to requirements of UK statutory Building Regulations and Technical Standards for Ventilation and BRE 398.
SAP Appendix Q tested
Exceeds requirements of Building Regulations Approved Document L (England & Wales).
EU RoHS Directive compliant.
Conforms to requirements of EC council directives relating to Electromagnetic Compatibility and Electrical Safety:
2006/95/EC (LVD), 2004/108/EC (EMC), EN 60335-1:2002/A2:2006, EN 60335-2- 80:2003/A1:2004.
CE and UKCA Marked.
Dimensions: 715mm wide x 490mm high (excluding ports) x 415mm deep (426mm with mounting bracket).

Weight: 24.5kg.
Finish: White Paint (RAL9016 Semi-gloss Traffic White).
Materials:
Housing: Zintec sheet steel housing, powder coated white.
Internals: Expanded polypropylene (EPP).
Heat exchanger: Polystyrene.
Internal insulation: Closed cell foamed Nitrile rubber, class ‘O’ fire rating.
Standard filters: Grade ISO Coarse 55% (G3) synthetic filters.
Guarantee period: 3 years (UK only).
Electrical: 230V ~ 50/60Hz, 5A fuse.
Installation: To be installed accordance with the relevant and applicable building regulations.
Maintenance: Service and filter replacement subject to local environment - see product manual.
Acoustics: Full acoustic data.
|
Exhaust terminal configuration*
|
Fan speed setting
|
Specific fan power (W/l/s)
|
Heat exchange efficiency (%)
|
Specific fan power (W/l/s)
|
Heat exchange efficiency (%)
|
|
2009
|
2012
|
||||
|
Kitchen + 2 additional wet rooms
|
100% variable
|
-
|
-
|
0.71
|
90%
|
|
Kitchen + 3 additional wet rooms
|
100% variable
|
0.67
|
90%
|
0.85
|
88%
|
|
Kitchen + 4 additional wet rooms
|
100% variable
|
0.77
|
89%
|
1.04
|
87%
|
|
Kitchen + 5 additional wet rooms
|
100% variable
|
0.87
|
88%
|
1.28
|
87%
|
|
Kitchen + 6 additional wet rooms
|
100% variable
|
1.02
|
87%
|
1.58
|
87%
|
|
Kitchen + 7 additional wet rooms
|
100% variable
|
1.2
|
87%
|
-
|
-
|


*@FID (0 Pa)
All units offer 100% variable speed control.
|
Product
|
% of Max flow
|
Airflow
|
dB(A) @ 3m Hemispherical
|
dB(A) @ 3m Spherical
|
||
|
Induct Inlet
|
Induct Outlet
|
Casing Breakout
|
Casing Breakout
|
|||
|
HRV3
Q Plus Eco |
33%
|
36l/s @ 12Pa
|
25
|
35
|
21
|
18
|
|
68%
|
73l/s @ 38Pa
|
36
|
49
|
29
|
26
|
|
|
100%
|
108l/s @ 100Pa
|
45
|
57
|
37
|
34
|
|
All acoustic data is third party tested at Sound Research Laboratories (SRL) Ltd.