Contact Sales 0800 970 4190
The new HRV20 HE Q Plus continuously running whole-house ventilation unit with heat recovery (MVHR) has been specifically designed to expand Titon’s current HRV range by offering airflows of up to 178 l/s (640m3/h).
Combining extremely low power consumption and a highly efficient heat exchanger (92%) specifically designed to enhance SAP performance via Appendix Q and can be incorporated into larger apartments or dwellings.
The HRV20 HE Q Plus Range of MVHR unit comes in two different models; the ‘HMB’ & ‘B’ models which are part of our Eco version range. Each set out to accommodate our customers’ needs.
Recognised and listed in the UK Product Characteristics Database and includes intelligent humidity options through controller options.
Product Model | Product Code | Energy Rating |
HRV20 HE Q Plus HMB Eco aura-t™ HMB ready – (Filter Door) |
TP652HMB/544 (left hand config) |
Energy Rating A |
TP652HMB/RH (right hand config) |
Product Model | Product Code | Energy Rating |
HRV20 HE Q Plus B Eco-aura controls ready – (Filter Door) |
TP653B/LH (left hand config) |
Energy Rating A+ |
TP653B/RH (right hand config) |
XP2010561 – ISO Coarse 65% (G4) bypass filter set fitted as standard.
XP2010929 – ISO Coarse 65% (G4)/ISO ePM1 75% (F7) filters available on request.
Conforms to requirements of UK statutory Building Regulations and Technical Standards for Ventilation and BRE 398
SAP Appendix Q tested
Exceeds requirements of Building Regulations Approved Document L (England & Wales)
EU RoHS Directive compliant.
Conforms to requirements of EC council directives relating to Electromagnetic Compatibility and Electrical Safety:
2006/95/EC (LVD), 2004/108/EC (EMC) EN 60335-1:2002/A2:2006, EN 60335-2- 80:2003/A1:2004.
CE and UKCA Marked.
Dimensions: 752mm wide x 708mm high (excluding ports) x 533mm deep (549mm with mounting bracket).
Weight: 46kg.
Finish: White Paint (RAL9016 Semi-gloss Traffic White).
Housing: Zintec sheet steel housing, powder coated white.
Internals: Expanded polypropylene (EPP).
Heat exchanger: Polystyrene.
Internal insulation: Closed cell foamed Nitrile rubber, class ‘O’ fire rating.
Standard filters: ISO Coarse 65% (G4).
Guarantee period: 3 years (UK only).
Electrical: 230V ~ 50/60Hz, 5A fuse.
Installation: To be installed accordance with the relevant and applicable building regulations.
Maintenance: Service and filter replacement subject to local environment – see product manual.
Acoustics: Full acoustic data.
Exhaust terminal configuration*
|
Fan speed setting
|
Specific fan power (W/l/s)
|
Heat exchange efficiency (%)
|
Specific fan power (W/l/s)
|
Heat exchange efficiency (%)
|
2009
|
2012
|
||||
Kitchen + 1 additional wet room
|
100% variable
|
0.52
|
92%
|
0.52
|
91%
|
Kitchen + 2 additional wet rooms
|
100% variable
|
0.48
|
91%
|
0.53
|
91%
|
Kitchen + 3 additional wet rooms
|
100% variable
|
0.48
|
91%
|
0.58
|
90%
|
Kitchen + 4 additional wet rooms
|
100% variable
|
0.53
|
90%
|
0.68
|
90%
|
Kitchen + 5 additional wet rooms
|
100% variable
|
0.58
|
90%
|
0.79
|
89%
|
Kitchen + 6 additional wet rooms
|
100% variable
|
0.66
|
90%
|
0.95
|
89%
|
Kitchen + 7 additional wet rooms
|
100% variable
|
0.76
|
89%
|
1.15
|
88%
|
Figures taken from the BRE Test Results.
*Number of wet rooms is based on SAP Q test criteria and does not correlate directly with regulatory performance requirements.
*@FID (0 Pa)
All units offer 100% variable speed control
Product
|
% of Max flow
|
Airflow
|
dB(A) @ 3m Hemispherical
|
dB(A) @ 3m Spherical | ||
Induct Inlet
|
Induct Outlet
|
Casing Breakout
|
Casing Breakout
|
|||
HRV20 HE Q Plus Eco
|
41%
|
65l/s @ 18Pa
|
33
|
43
|
27
|
24
|
65%
|
116l/s @ 51Pa
|
46
|
58
|
42
|
39
|
|
100%
|
170l/s @ 100Pa
|
57
|
70
|
49
|
46
|
All acoustic data is third party tested at Sound Research Laboratories (SRL) Ltd.