Contact Sales 0800 970 4190
The H200 Q Plus continuously running horizontal whole-house ventilation unit with heat recovery is independently tested by the BRE. It is ideal for flats due to its low profile.
Combining low power consumption and a highly efficient heat exchanger, this unit enhances SAP performance via Appendix Q and remains versatile enough in size to be equally functional in large through to small apartments alike.
The H200 Q Plus Range of MVHR unit comes in two different models; the ‘HMB’ & ‘B’ models which are part of our Eco version range. Each set out to accommodate our customers’ needs.
The H200 Q Plus comes in Eco versions only with a 100% airflow diverting Summer Bypass, recognised and listed in the UK Product Characteristics Database. They also include intelligent humidity options and can be fitted with the auralite® status indicator, aura-t™ (HMB and B models), auramode® and aurastat® controllers (B models only).
| Product Model | Product Code | Energy Rating | 
| H200 Q Plus HMB Eco auralite® & aura-t™ ready - 204x60  | 
TP451HMB | Energy Rating A | 
| H200 Q Plus HMB Eco auralite® & aura-t™ ready - Ø160  | 
TP453HMB | Energy Rating A | 
| H200 Q Plus HMB Eco auralite® & aura-t™ ready - Ø150  | 
TP452HMB | Energy Rating A | 
| Product Model | Product Code | Energy Rating | 
| H200 Q Plus B Eco-aura controls ready - 204x60  | 
TP461B/ TP461BC (Cold Climate Option)  | 
Energy Rating A | 
| H200 Q Plus B Eco-aura controls ready - Ø160  | 
TP463B/ TP463BC (Cold Climate Option)  | 
Energy Rating A | 
| H200 Q Plus B Eco-aura controls ready - Ø150  | 
TP462B/ TP462BC (Cold Climate Option)  | 
Energy Rating A | 
XP2010173– ISO Coarse 85% (G4) filter set fitted as standard.
XP2010174 - ISO ePM1 55% (F7) and ISO Coarse 85% (G4) filters available on request.
Conforms to requirements of UK statutory Building Regulations and Technical Standards for Ventilation and BRE 398.
SAP Appendix Q tested
Exceeds requirements of Building Regulations Approved Document L (England & Wales).
EU RoHS Directive compliant.
Conforms to requirements of EC council directives relating to Electromagnetic Compatibility and Electrical Safety: 
2006/95/EC (LVD), 2004/108/EC (EMC), EN 60335-1:2002/A2:2006, EN 60335-2- 80:2003/A1:2004.
CE Marked.

Dimensions: 1000mm wide (excluding ports) x 200mm high x 600mm deep.
Weight: 32kg.
Finish: White Paint (RAL9016 Semi-gloss Traffic White).
Housing: Zintec sheet steel housing, powder coated white.
Internal insulation: Closed cell foamed Nitrile rubber, class ‘O’ fire rating.
Heat exchanger: aluminium.
Standard filters: Grade ISO Coarse 85% (G4) pleated panel filters.
Guarantee period: 3 years (UK only).
Electrical: 230V ~ 50/60Hz, 3A fuse.
Installation: To be installed accordance with the relevant and applicable building regulations.
Maintenance: Service and filter replacement subject to local environment – see product manual.
Acoustics: Full acoustic data.
| 
 Exhaust terminal configuration* 
 | 
 Fan speed setting 
 | 
 Specific fan power (W/l/s) 
 | 
 Heat exchange efficiency (%) 
 | 
 Specific fan power (W/l/s) 
 | 
 Heat exchange efficiency (%) 
 | 
| 
 2009 
 | 
 2012  
 | 
||||
| 
 Kitchen + 1 additional wet room 
 | 
 100% variable 
 | 
 0.58 
 | 
 83% 
 | 
 0.58 
 | 
 83% 
 | 
| 
 Kitchen + 2 additional wet rooms 
 | 
 100% variable 
 | 
 0.55 
 | 
 83% 
 | 
 0.66 
 | 
 82% 
 | 
| 
 Kitchen + 3 additional wet rooms 
 | 
 100% variable 
 | 
 0.61 
 | 
 82% 
 | 
 0.8 
 | 
 80% 
 | 
| 
 Kitchen + 4 additional wet rooms 
 | 
 100% variable 
 | 
 0.72 
 | 
 81% 
 | 
 1.01 
 | 
 80% 
 | 
| 
 Kitchen + 5 additional wet rooms 
 | 
 100% variable 
 | 
 0.85 
 | 
 80% 
 | 
 1.25 
 | 
 80% 
 | 
| 
 Kitchen + 6 additional wet rooms 
 | 
 100% variable 
 | 
 0.99 
 | 
 80% 
 | 
 1.58 
 | 
 82% 
 | 
| 
 Kitchen + 7 additional wet rooms 
 | 
 100% variable 
 | 
 1.2 
 | 
 80% 
 | 
 - 
 | 
 - 
 | 
Figures taken from the BRE Test Results.
*Number of wet rooms is based on SAP Q test criteria and does not correlate directly with regulatory performance requirements.

*@FID (0 Pa)
All units offer 100% variable speed control
| 
 Product 
 | 
 % of Max flow 
 | 
 Airflow 
 | 
 dB(A) @ 3m Hemispherical 
 | 
 dB(A) @ 3m Spherical 
 | 
||
| 
 Induct Inlet 
 | 
 Induct Outlet 
 | 
 Casing Breakout 
 | 
 Casing Breakout 
 | 
|||
| 
 HRV200 Q Plus Eco 
 | 
 47% 
 | 
 39l/s @ 20Pa 
 | 
 25 
 | 
 37 
 | 
 25 
 | 
 22 
 | 
| 
 64% 
 | 
 53l/s @ 37Pa 
 | 
 30 
 | 
 21 
 | 
 31 
 | 
 28 
 | 
|
| 
 100% 
 | 
 83l/s @ 100Pa 
 | 
 39 
 | 
 54 
 | 
 41 
 | 
 38 
 | 
|
All acoustic data is third party tested at Sound Research Laboratories (SRL) Ltd.