Fire Sleeve – Ducting

Ducting

Fire Sleeves prevent the spread of fire where plastic pipes or plastic ducts penetrate fire compartment walls.

QRS110/54,QRS205/60,QRS220/90,QRS110*,QRS130*,QRS 75,QRS 90*

Features & Benefits

  • Tested to BSEN 1366-3: 2009
  • Tested with Uncapped/Uncapped (U/U) duct configurations as required for ventilation ducts
  • Up to 2 hour fire rating
  • Suitable for masonry walls or plasterboard partitions
  • Suitable for insulated and non-insulated partitions
  • Can be retrofitted
  • No mechanical fixings required
  • Robust galvanised steel shell
  • Performance unaffected by weathering (Type X Durability)

Technical Information

Product Codes and Specific features

Building Regulations impose limitations on all pipes passing through fire compartment walls and floors. QRS Intumescent Fire Sleeves allow plastic ducts to meet the requirements of the Building Regulations. QRS Intumescent Fire Sleeves have been tested according to BSEN 1366-3: 2009 where various plastic duct sizes have met insulation and integrity criteria for this standard for up to 2 hours.

The QRS Intumescent Fire Sleeves consist of a flexible galvanised steel shell containing graphite based intumescent material.
They are manufactured to suit flat ducts of 110x54mm, 204x60mm, and 220x90mm. And round ducts with 100mm and 125mm overall diameter.

Tested to Type X durability which means the QRS Fire Sleeves can be installed in conditions exposed to weathering. QRS CE/UKCA Marked Fire Sleeves are expected to last the lifetime of the building.

The QRS Intumescent Fire Sleeve should be placed around the ventilation duct, positioned centrally within the partition and should be flush or protrude from each face of the wall. The plasterboard should be cut to a tight fit around the QRS Intumescent Fire Sleeve, and any gaps should be sealed with the Quelstop Intumescent Acrylic Sealant, part number QSS310.

For all sleeve types, please refer to manufacturers installation guidance prior to system design or installation.

Product Code Duct Size (mm) Space needed around duct to fit QRS Sleeve (mm) Recommended aperture
 (mm)
QRS length
(mm)
Fire
Rating
QRS110/54 110 x 54 9 130 x 73 140 120 minutes
QRS205/60 204 x 60 9 225 x 80 180 120 minutes
QRS220/90 220 x 90 18 256 x 126 140 120 minutes
QRS110* 100 10 130 180 120 minutes
QRS130* 125 20 170 180 90 minutes
QRS 75 75 Semi rigid 8 90 140 120 minutes
QRS 90* 90 Semi Rigid 13 116 140 120 minutes

* QRS110, QRS130 and QRS 90 are not currently CE Marked