Contact Sales 0800 970 4190
The CME2.1 Q Plus is ideal for continuous extract of stale, damp and polluted air to the outside environment.
The combination of aesthetic smooth lines, unique tilted impeller and single level ports provides the ideal solution for hidden ceiling installation in flats and apartments.
The unit has a very large duty range over 103 l/s (371 m3/hr) at 200 Pa.
Volt free switch inputs
TP312A – CME 2.1 Q Plus (Full assembly).
TP312HA – CME 2.1 Q Plus, humidity sensor (Full assembly).
TP313A – CME 2.1 Q Plus (Second fix).
TP313HA – CME 2.1 Q Plus, humidity sensor (Second fix).
Switch live inputs
TP312HALS – CME 2.1 Q Plus, humidity sensor, switch live inputs (Full assembly).
TP313HALS – CME 2.1 Q Plus, humidity sensor, switch live inputs (Second fix).
TP325 – CME base only (First fix).
Volt free switch inputs
TP312A – CME 2.1 Q Plus (Full assembly).
TP312HA – CME 2.1 Q Plus, humidity sensor (Full assembly).
TP313A – CME 2.1 Q Plus (Second fix).
TP313HA – CME 2.1 Q Plus, humidity sensor (Second fix).
Switch live inputs
TP312HALS – CME 2.1 Q Plus, humidity sensor, switch live inputs (Full assembly).
TP313HALS – CME 2.1 Q Plus, humidity sensor, switch live inputs (Second fix).
Indicator Ready (auralite® CME – TP517)
TP312CH – CME 2.1 Q Plus, humidity sensor, controls ready (Full assembly).
TP313CH – CME 2.1 Q Plus, humidity sensor, controls ready (Second fix).
Conforms to requirements of UK statutory Building Regulations and Technical Standards for Ventilation and BRE 398.
SAP Appendix Q tested
Exceeds requirements of Building Regulations Approved Document L (England & Wales).
EU RoHS Directive compliant.
Conforms to requirements of EC council directives relating to Electromagnetic Compatibility and Electrical Safety:
2006/95/EC (LVD), 2004/108/EC (EMC) EN 60335-1:2002/A2:2006, EN 60335-2- 80:2003, A1:2004.CE Marked.
Other non-UK info available on request.
Dimensions (excluding ports): 355mm wide x 421mm long x 252mm high
Dimensions in mm.
Weight: 5kg
Finish: Light grey / dark grey
Materials;
Housing: Talc Filled Polypropylene
Guarantee period: 3 years (UK only)
Electrical: 230V ~ 50/60Hz, 3A fuse
Installation: To be installed accordance with the relevant and applicable building regulations.
Maintenance: See product manual.
Acoustics: Full acoustic data.
Exhaust terminal configuration*
|
Fan speed setting
|
Specific fan power (W/l/s)
|
Specific fan power
(W/l/s) |
2009
|
2012
|
||
Kitchen + 1 additional wet room
|
100% variable
|
0.20
|
0.20 |
Kitchen + 2 additional wet rooms
|
100% variable
|
0.18
|
0.18 |
Kitchen + 3 additional wet rooms
|
100% variable
|
0.20
|
0.20 |
Kitchen + 4 additional wet rooms
|
100% variable
|
0.22
|
0.22 |
Kitchen + 5 additional wet rooms
|
100% variable
|
0.28
|
0.28 |
Kitchen + 6 additional wet rooms
|
100% variable
|
0.33
|
0.33
|
Figures taken from the BRE Test Results.
*Number of wet rooms is based on SAP Q test criteria and does not correlate directly with regulatory performance requirements.
Test results available for use with 110 x 54mm ducting.
Airflow
l/s |
% of
Max flow |
dB(A) @
3m Hemispherical |
dB(A) @ 3m Spherical
|
|
Induct
Inlet |
Casing
Breakout |
Casing
Breakout |
||
36 l/s
|
41%
|
19
|
25
|
22
|
60 l/s
|
68%
|
31
|
38
|
35
|
88 l/s
|
100%
|
40
|
47
|
44
|
Call me back
Login
Basket