The Titon Trimbox NO2 Filter® reduces Nitrogen Dioxide (NO2) which is predominantly produced by exhaust gases from diesel engines.
Due to this pollution arising in cities and urban areas there is a need to implement mitigation measures to improve the indoor air quality (IAQ). The Trimbox NO2 Filter® is an effective means of reducing high NO2 to an acceptable mean annual concentration level of 40µg/m³.
In addition to outstanding NO2 reductions, the Titon Trimbox active carbon filters also absorb sulphur dioxide, hydrogen sulphide, hydrogen chloride, ammonia odours, volatile organic compounds and solvents.

220 x 90 - TP550
Ø160 - TP552
Ø150 - TP554
Removable insulation jacket*: 220x90mm ports - XP9910248 150 or 160mm ports - XP9910305
*Advised to fit before install completed.
ISO ePM1 55% (F7) pre filter (ISO Coarse 60% (G4) standard in units) - XP2010121
Behind unit duct mounting kit - TP558
Dimensions: 350mm wide x 690mm high (excluding ports) x 205mm deep
Port Dimension: 220mm x 90mm, Ø150mm, Ø160mm

Weight:
Trimbox No2 - 17 Kg
Insulation Jacket - 2.8 Kg
Finish: White Paint
Materials:
Housing: Zintec sheet steel housing, powder coated white
Internals: Zintec sheet steel
Pre-Filter: Grade ISO Coarse 60% (G4) synthetic filters as standard, ISO ePM1 55% (F7) optional
Active Carbon Filter: Honeycomb matrix constructed filter filled with granular active carbon
Internal insulation: Closed cell foamed nitrile rubber, class ‘O’ fire rating
Duct Ports: Plastic
Installation: Install in accordance with regulatory requirements, such as the Domestic Ventilation Compliance Guide (England & Wales) and the Residential Ventilation Association recommendations
These units can be installed either vertically or horizontally
Maintenance: Service and filter cleaning/replacement subject to local environment – see product manual
Accessories: Replacement pre-filters and active carbon filters
Third party tested for both NO2 and acoustic reductions based around the standards currently in place for health as specified by the World Health Organisation and the European Union.
Testing references:
COSHH - Workplace exposure limits
COMEAP - Government guidance regarding health of air pollution
WHO - World Health Organisation
(Based on nitrogen dioxide pre filter concentrations of ≈ 200μg m3)
|
Airflow rate (l/S)
|
Filter pressure drop (Pa)
|
Concentration reduction (%)
|
| Trimbox NO2 Filter | ||
|
29
|
31
|
97.6
|
|
80.3
|
134
|
97.9
|
Independently tested at SRL, report reference C/23276/TO5 to BS EN ISO 7235:2009
| Description |
Octave Band (Hz) Static Insertion Loss, dB
|
|||||||
|
63
|
125
|
250
|
500
|
1000
|
2000
|
4000
|
8000
|
|
| Trimbox NO2 Filter |
6.5
|
7.6
|
4.9
|
8.6
|
16.1
|
26.8
|
32.9
|
36
|
ISO Coarse 60% (G4) Prefilter